Telefon:+36-20-9729663
E-mail:adam@hgd.hu
Elérhetõségek
  • English
  • Deutsch
  • Magyar
Reine Energie Reinertrag

Family house with 40 kW heat pump system

The heat and cool demand of this building are 40 and 20 kW, so an IVT Greenline heat pump was installed with 41,5 kW nominal performance

 

This heat pump supplies the domestic hot water demand, too and it has a weather-dependent regulator.
There are 7 pieces BHEs with 100 m depth on the primary side of this system. The pipes are single BHE with 40 mm diameter and the primary side is filled with ethylene glycol and water. The grouting material is bentonite-cement. This system utilized ~ 32 kW geothermal heat.
The free-cooling is done by heat exchanger on the primary side. The heat pump makes domestic hot water in a 500-liter tank.
According to the plan this heat pump system was installed by the HGD Ltd.

Angewandte Technologie: 
Wärmepumpe-System mit Erdwärmekollektoren
Stadt: 
Kulcs
Heizungsleistung: 
40 kW
Kühlungsleistung: 
20 kW